10 kV户外开关柜高压触点无线温度测量系统的设计
Design of 10 kV outdoor switchgear high-voltage contact wireless temperature monitoring system
-
摘要: 针对户外开关柜高压触点温度测量易受环境影响、精度较低等问题,设计了10 kV户外开关柜高压触点无线温度测量系统.该系统以无线射频单片机CC2530F256为核心部件,利用ZigBee网络的自组织性,将温度测量终端节点与手持式协调器节点组网,实现户外开关柜高压触点温度的精确测量和数据的无线传输.实验结果表明,该系统受环境影响较小,且测得的温度数据误差小于1℃,可满足户外开关柜高压触点在线监测的要求.Abstract: Aiming at the problems of outdoor switchgear high-voltage contact temperature measurement such as vulnerability to environmental impact and low precision, the 10 kV outdoor switchgear high-voltage contact wireless temperature monitoring system was designed.The system selected the wireless RF MCU CC2530F256 as the core chip, using the self organizing of ZigBee network, through temperature measurement terminal node and handheld coordinator node of the network, realized the outdoor switchgear high-voltage contact temperature data precision measurement and wireless transmission.Experimental results showed that the system was not easy to be affected by the environment, and the measured data error was less than 1℃.It could satisfy the requirement of outdoor switchgear high-voltage contact temperature online monitoring.
-
-
[1]
王秉政,江建武,赵灵.高压开关柜接触发热温度场数值计算[J].高压电器,2013,49(12):42.
-
[2]
陈平,薛毓强,郭建钊.大电流母排三维涡流场-温度场耦合分析[J].电力科学与技术学报,2009,24(3):68.
-
[3]
刘宗信,张加善.固定式高低压开关柜中载流节点发热问题的浅析[J].吉林电力技术,1995,35(2):57.
-
[4]
潘长明,刘刚,熊炬,等.高压开关柜绝缘事故的分析及防范措施[J].高压电器,2011,47(7):90.
-
[5]
王小强,欧阳骏,黄宁淋.ZigBee无线传感器网络设计与实现[M].北京:化学工业出版社,2012:3-15,31-33
,134-135,213-216. -
[6]
杨书杰,张贤跃.高压侧测量用电源设计[J].电力自动化设备,2009,29(12):13.
-
[7]
杨增汪,王宜怀,戴新宇.基于ZigBee和GPRS的高压开关柜无线监测系统设计[J].电力系统保护与控制,2010,38(23):203.
-
[8]
陈宝怡.红外诊断技术在高压断路器内部发热故障中的应用[J].高压电器,2011,47(5):92.
-
[1]
计量
- PDF下载量: 60
- 文章访问数: 1087
- 引证文献数: 0